WD4XETH2 ETHERNET COMMUNICATION CARD: INSTALLATION AND NETWORK SETUP

Learn how to install the WD4XETH2 single-port Ethernet communication card, select a protocol, configure network parameters, and check basic communication status on a WD4X inverter.

Applies to
  • WD4X inverters fitted with the WD4XETH2 Ethernet communication card.
  • Modbus/TCP and EtherNet/IP communication.

This article is a practical introduction based on the WD4XETH2 user manual printed April 2023. It does not replace the full manual, installation diagrams, or the WD4X inverter’s safety instructions.

Download the WD4XETH2 Installation and Operation Manual

Important safety precautions

Warning: Disconnect the inverter’s power supply before installing or removing the communication card or connecting the communication network. Wait until the power supply is fully discharged before removing the card. Installing or removing the module while energized can damage the inverter. Follow the WD4X inverter manual’s discharge and electrical safety procedures.

  • Turn off inverter power before changing the communication cable.
  • Handle the module carefully. Static electricity can damage its CMOS components.
  • Make sure the communication module connector is correctly seated.
  • Check parameter units before entering values.
  • Do not execute CM-94 Comm Update while the inverter is running or during cyclic communication.
What the card supports

The WD4XETH2 connects a WD4X inverter to an Ethernet network for control and monitoring by a PLC or another client device.

  • Protocols: Modbus/TCP or EtherNet/IP, selected using switch 1.
  • Communication speeds: 10 Mbps and 100 Mbps.
  • Auto-negotiation: supported.
  • Network cable: Category 5, as specified in the manual.
  • Maximum node-to-hub distance: 100 m.
1. Install the communication card

Before starting, confirm that the kit includes the Ethernet module, two supplied brass standoffs, and two M3 × L8 fixing screws. Refer to section 2.3 of the manual for installation images.

With inverter power disconnected and fully discharged:

  1. Loosen the cover screws and remove the cover.
  2. Disconnect the keypad connector.
  3. Remove the keypad adapter PCB, carefully releasing its plastic tabs.
  4. Install the two standoffs supplied with the Ethernet card kit.
  5. Fit the Ethernet card.
  6. Secure the card to the standoffs using the two supplied screws.
  7. Snap the keypad adapter PCB into place above the Ethernet card.
  8. Reconnect the keypad connector cable.
  9. Connect the network cable and reinstall the front cover.
2. Select the communication protocol

Use switch 1, located beside the Ethernet connector.

Switches 2, 3, and 4 are not used.

Changing the switch while the module is operating does not immediately change the protocol. The module reads the switch setting at power-up or when communication is reinitialized using Comm Update. Observe the safety restrictions above before making changes.

3. Configure the network address

The module supports IPv4. Enter each address as four separate decimal values, with each value between 0 and 255.

Use the IP address, subnet mask, and gateway assigned for your installation. Do not use 0.0.0.0 or 255.255.255.255 as the module’s IP address. Check that the address does not conflict with another device on the network.

Set Ethernet speed

Automatic selection negotiates the highest available network speed.

Apply changes

Changed communication parameters are not applied immediately. With the inverter stopped and cyclic communication inactive, set CM-94 Comm Update to 1 (Yes) to apply the changes and restart Ethernet communication.

4. Configure the client or PLC

Modbus/TCP

The PLC, HMI, or PC acts as the client, and the inverter acts as the server. The module supports these functions:

The documented multiple-register read and write operations support 1 to 16 registers. Use the manual and WD4X parameter documentation for register addresses, permitted values, and frame details.

EtherNet/IP

For cyclic I/O communication, configure the PLC’s assembly instances to match the inverter settings:

  • CM-29: input instance selection for inverter status sent to the client.
  • CM-49: output instance selection for commands sent to the inverter.

The keypad selection value is not the same as the assembly instance number. Refer to sections 4.5, 4.6, and 6.2 of the manual for the correct instance numbers and data sizes.

For configurable parameter assemblies, the manual describes status addresses in CM-31 through CM-38 and control addresses in CM-51 through CM-58. Match the number of mapped parameters to the selected assembly.

5. Check the communication LEDs

The SPEED and LINK indicators operate the same way for both protocols.

For Modbus/TCP, a flashing green CPU indicator means the module CPU is operating normally. For EtherNet/IP, a green MS indicator means the module is normal, and a steady green NS indicator indicates an established Class 1 I/O connection.

For other colors or flashing patterns, refer to the protocol-specific LED tables in sections 3.3 and 3.4 of the manual before taking corrective action.

Troubleshoot common issues

No Ethernet link

Check the network cable and wiring. Turn off inverter power before changing the communication cable.

Invalid or duplicate IP address

Check the configured address, confirm that it is unique on the network, and avoid 0.0.0.0 and 255.255.255.255. Apply corrections using CM-94 only when the inverter is stopped and cyclic communication is inactive.

Changed settings have not taken effect

Communication parameter changes require Comm Update. Confirm that CM-94 has been executed under the safe conditions described above.

EtherNet/IP I/O connection is not established

Check the network connection and confirm that the PLC’s input/output assembly numbers and data sizes match CM-29 and CM-49. Consult the manual’s EtherNet/IP connection and LED guidance.

Review lost-command behavior before operation

The inverter’s response to a communication loss is configured using:

  • Pr-12 Lost Cmd Mode: action taken after a lost command.
  • Pr-13 Lost Cmd Time: delay before the configured action.
  • Pr-14 Lost Preset F: frequency used when Lost Preset mode is selected.

The manual lists None, Free-Run, Dec, Hold Input, Hold Output, and Lost Preset modes. Some modes maintain operation rather than stop the motor. Select and validate the appropriate response for the application before putting equipment into service.

Refer to section 7 of the manual for protocol-specific lost-command detection and mode descriptions.

Need additional help?

For installation diagrams, complete assembly mappings, communication frames, object definitions, and warranty terms, use the full WD4XETH2 manual.